Siemens 6AV6355-1AA47-7CA0 OP 77A
€ 1.995,00
The Siemens 6AV6355-1AA47-7CA0 is an operator panel belonging to the OP 77A series, part of the SIMATIC HMI Basic Panels product family manufactured by Siemens. This compact panel operator unit is designed for straightforward machine-level human-machine interface tasks, providing a keypad-based interface for process visualization and control. It is a member of the SIMATIC HMI line, intended for use in cost-sensitive applications where a full graphical touchscreen is not required.
The OP 77A features a monochrome LCD display and a membrane keypad for operator input, offering a reliable and robust interface for industrial environments. It supports the MPI and PROFIBUS DP communication interfaces, enabling direct integration with Siemens SIMATIC S7-200, S7-300, and S7-400 PLCs. The panel is configured using WinCC flexible software and supports recipe management, alarm logging, and trend display functions within its onboard memory capacity. Its compact housing is rated to IP65 on the front face, providing protection against dust and water ingress in panel-mounted installations.
The OP 77A is commonly deployed in machine building, manufacturing automation, and process control applications where a simple, reliable operator interface is needed at the machine level. It is well suited for controlling conveyor systems, packaging machinery, and general-purpose industrial equipment. The panel's compatibility with the SIMATIC S7 controller family and its straightforward configuration make it a practical choice for OEMs and system integrators working within the Siemens automation ecosystem.
Technical Specifications
| Display Type | Monochrome LCD |
|---|---|
| Display Size | 4 inches |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | 4.5 W (typical) |
| Communication Interface | MPI, PROFIBUS DP |
| IP Rating (Front) | IP65 |
| IP Rating (Rear) | IP20 |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 10% to 90% (non-condensing) |
| Mounting | Panel mounting |
| Certifications | CE, UL, cULus |
| Configuration Software | WinCC flexible 2008 or later |
| Series/Product Family | SIMATIC HMI OP 77A |
Common Error Codes & System Events
- Event ID: 10000
- Communication error between the HMI panel and the connected PLC. The panel cannot establish or maintain a connection to the controller.
Check MPI or PROFIBUS DP cable connections and termination resistors. Verify the PLC address settings match the HMI project configuration. Ensure the PLC is powered and in RUN mode. - Event ID: 10001
- Connection to the PLC was interrupted during operation.
Inspect communication cables for damage or loose connectors. Check bus termination and cable shielding. Restart the HMI panel and verify PLC status. - Event ID: 20000
- Project download error. The configuration project could not be transferred to the panel successfully.
Verify the USB or serial transfer cable is correctly connected. Ensure WinCC flexible project settings match the target panel type and firmware version. Retry the download. - Event ID: 40000
- System memory low. The panel's available memory for runtime operation is insufficient.
Reduce the number of active alarms, recipes, or trend data stored on the device. Archive or delete old data logs and restart the panel. - Event ID: 50000
- Firmware version mismatch between the HMI panel and the loaded project.
Update the panel firmware using ProSave or WinCC flexible to match the version required by the project. Re-download the project after updating firmware. - Event ID: 60000
- Internal device error or hardware fault detected during self-test at startup.
Perform a factory reset via the panel's Start Center. If the error persists after reset and re-download, the panel hardware may require repair or replacement.
Frequently Asked Questions
Which PLCs are compatible with the OP 77A (6AV6355-1AA47-7CA0)?
The OP 77A is compatible with Siemens SIMATIC S7-200, S7-300, and S7-400 PLCs via MPI or PROFIBUS DP communication interfaces. It can also communicate with S7-200 via PPI protocol.
What software is used to configure the OP 77A?
The OP 77A is configured using Siemens WinCC flexible 2008 or a compatible version. Projects are downloaded to the panel via a PC adapter cable or USB-to-serial adapter.
What is the supply voltage for the 6AV6355-1AA47-7CA0?
The panel operates on a 24 V DC supply voltage. Ensure the power supply is within the specified tolerance range to avoid operational issues.
What is the front panel protection rating of the OP 77A?
The front face of the OP 77A is rated IP65, providing full protection against dust and protection against low-pressure water jets, making it suitable for panel-mounted industrial installations.
Can the OP 77A display graphical trend curves?
The OP 77A supports basic trend display functionality within its monochrome LCD interface, allowing operators to monitor process variable trends configured in the WinCC flexible project.
Troubleshooting
Display remains blank after power is applied
Check the 24 V DC supply voltage at the panel power connector using a multimeter. Verify the supply is within tolerance and that the connector is fully seated.
Restore correct 24 V DC supply voltage. If voltage is correct and the display remains blank, inspect the internal backlight or power supply board. The panel may require professional repair or backlight replacement.
HMI panel cannot communicate with the PLC
Verify the MPI or PROFIBUS DP cable is correctly wired and terminated. Check that the bus address configured in the HMI project matches the physical address set on the PLC. Use a bus diagnostic tool to check for bus errors.
Correct any wiring faults, ensure proper bus termination at both ends of the cable, and confirm matching address settings in both the PLC and the HMI project. Re-download the project if configuration changes are made.
Project download fails or transfer is interrupted
Check the transfer cable connection between the PC and the panel. Confirm the panel is in Transfer mode via the Start Center menu. Verify that the WinCC flexible project is compiled without errors.
Restart the panel in Transfer mode, use a known-good transfer cable, and re-attempt the download. Ensure the PC COM port or USB adapter drivers are correctly installed.
Panel displays 'No project' message after startup
The panel's internal flash memory may not contain a valid project, or the project was lost due to a firmware update or factory reset.
Re-download the WinCC flexible project to the panel using the correct transfer method. Ensure the project is compiled for the correct panel type before transfer.
Keypad buttons are unresponsive or intermittently fail
Inspect the membrane keypad for physical damage, contamination, or wear. Check for any debris under the keypad surface that may be preventing actuation.
Clean the keypad surface with a dry cloth. If individual keys remain unresponsive, the membrane keypad assembly may need to be replaced. Contact a qualified repair technician for keypad replacement.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV6640-0CA01-0AX0 OP 73micro
€ 279,00 – € 444,13Price range: € 279,00 through € 444,13Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1QK00-0AX0 OP27
€ 649,00 – € 869,00Price range: € 649,00 through € 869,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177
€ 1.247,00Select options This product has multiple variants. The options may be chosen on the product page