Siemens 6AV6343-0AA14-0CB6 OP 177B
€ 1.995,00
The Siemens 6AV6343-0AA14-0CB6 is an Operator Panel (OP 177B) belonging to the SIMATIC HMI series, designed for machine-level human-machine interface applications. This unit provides a monochrome STN display and is part of the Mobile Panel and Comfort Panel ecosystem within Siemens' broader SIMATIC HMI portfolio. It serves as a compact operator panel for visualizing process data and controlling industrial machinery directly at the machine level.
The OP 177B features a 5.7-inch STN monochrome display with a resolution of 320 x 240 pixels and supports both touch and key-based operation through its integrated membrane keypad. It is equipped with MPI/PROFIBUS DP and RS-422/RS-485 interfaces for communication with SIMATIC S7 PLCs and other compatible controllers. The panel runs on WinCC flexible runtime software, supports recipe management, alarm logging, and trend displays, and includes 512 KB of user memory for project data storage.
The OP 177B is widely deployed in manufacturing automation, packaging machinery, conveyor systems, and process control installations where a robust, panel-mount HMI with direct PLC connectivity is required. Its compatibility with SIMATIC S7-200, S7-300, and S7-400 PLCs makes it a versatile choice for both new installations and retrofit projects in discrete and process manufacturing environments.
Technical Specifications
| Display Size | 5.7 inch |
|---|---|
| Display Type | STN monochrome |
| Display Resolution | 320 x 240 pixels (QVGA) |
| Display Colors | Monochrome (blue/white) |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | Max. 9 W |
| Communication Interface | MPI/PROFIBUS DP, RS-422/RS-485 |
| User Memory | 512 KB |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 10% to 90% (non-condensing) |
| IP/Protection Rating | IP65 (front), IP20 (rear) |
| Mounting | Panel mounting |
| Certifications | CE, UL, cULus |
| Series/Product Family | SIMATIC HMI OP 177B |
Common Error Codes & System Events
- Event ID: 10000
- Communication error between the HMI panel and the connected PLC. The connection to the configured controller cannot be established or has been lost.
Check MPI/PROFIBUS DP cable connections and termination resistors. Verify the PLC address and baud rate settings match the HMI project configuration. Restart both the HMI and PLC if necessary. - Event ID: 10001
- Timeout error on the communication link. The HMI did not receive a response from the PLC within the configured timeout period.
Check network cabling and connectors. Verify the PLC is in RUN mode and that the configured station address is correct. Reduce network load if multiple devices share the bus. - Event ID: 20000
- Project download error. The project transfer from the engineering PC to the HMI panel failed or was interrupted.
Verify the transfer cable connection and PC communication settings. Ensure WinCC flexible is configured for the correct transfer interface. Retry the download after restarting the panel in transfer mode. - Event ID: 40000
- Configuration error detected in the loaded project. A tag or screen reference in the project is invalid or missing.
Open the project in WinCC flexible, check for compilation errors, and verify all tag connections and screen references are valid. Recompile and re-download the project. - Event ID: 50000
- Internal device error. A hardware or firmware fault has been detected within the HMI panel.
Perform a power cycle. If the error persists, reset the panel to factory defaults via the Control Panel settings. Contact Siemens technical support if the fault recurs. - Event ID: 70000
- Memory error. Insufficient user memory available to load the project or log data.
Reduce the project size, limit the number of archived values, or clear existing log data. Ensure the project memory requirements do not exceed the 512 KB user memory limit. - Event ID: 110000
- Printer communication error. The HMI cannot communicate with the configured printer.
Check the printer connection and ensure the correct printer driver is configured in the HMI project. Verify the interface settings match the connected printer.
Frequently Asked Questions
Which PLCs are compatible with the Siemens OP 177B (6AV6343-0AA14-0CB6)?
The OP 177B is compatible with SIMATIC S7-200, S7-300, and S7-400 PLCs via MPI or PROFIBUS DP. It also supports communication with S5 controllers and third-party controllers via the RS-422/RS-485 interface using appropriate drivers in WinCC flexible.
What software is required to program and configure the OP 177B?
The OP 177B is configured using Siemens WinCC flexible 2005 or later. Projects are created on a PC and transferred to the panel via MPI, PROFIBUS DP, or a serial connection.
What is the supply voltage for the OP 177B?
The OP 177B operates on 24 V DC. Ensure the power supply is within the permissible voltage tolerance range as specified in the device manual.
Does the OP 177B support recipe management and alarm logging?
Yes, the OP 177B supports recipe management, alarm logging, and trend displays as part of its WinCC flexible runtime functionality. These features are configured within the WinCC flexible engineering software.
What is the front panel protection rating of the OP 177B?
The front panel of the OP 177B carries an IP65 protection rating, making it suitable for panel-mount installations where dust and water jet protection is required.
Troubleshooting
Display remains blank after power on
Check that 24 V DC is present at the power supply terminals. Measure voltage at the panel connector to confirm supply integrity. Inspect the internal fuse if accessible.
Verify and restore the 24 V DC supply. If the supply is confirmed correct and the display remains blank, the internal power supply board or backlight may be faulty and the unit should be sent for repair or the backlight replaced.
HMI shows 'No connection to PLC' or communication error on startup
Check the MPI or PROFIBUS DP cable connections at both the HMI and PLC ends. Verify bus termination is correctly applied at both ends of the network segment. Confirm the PLC station address and baud rate match the HMI project settings.
Reseat all connectors, replace damaged cables, and ensure correct bus termination. Correct any address or baud rate mismatches in the WinCC flexible project and re-download. Restart both devices after making changes.
Touchscreen or keypad inputs are not responding
Check whether the panel is in transfer mode, which disables normal operation. Verify the project is correctly loaded and running. For keypad issues, inspect the membrane keypad connector internally for damage or corrosion.
Exit transfer mode via the Control Panel if active. Re-download the project if it is corrupted. If the keypad membrane is physically damaged, the front panel assembly should be replaced.
Panel repeatedly restarts or enters a boot loop
This may indicate a corrupted project file or a failing internal flash memory. Observe whether the panel reaches the WinCC flexible runtime screen before restarting.
Boot the panel into the Control Panel (Service menu) and perform a factory reset. Re-download a freshly compiled project from WinCC flexible. If the issue persists, the internal flash storage may be defective and the unit requires hardware repair.
Project download fails or transfer is interrupted
Check the transfer cable and the interface selected in WinCC flexible (MPI, PROFIBUS, or serial). Ensure the panel is set to transfer mode via the Control Panel before initiating the download.
Switch the panel to transfer mode, verify the correct COM port or network interface is selected in WinCC flexible, and retry the transfer. Replace the transfer cable if communication errors persist.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV3627-1QK00-0AX0 OP27
€ 649,00 – € 869,00Price range: € 649,00 through € 869,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AG1642-0BD01-4AX0 TP177B
€ 555,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177
€ 1.247,00Select options This product has multiple variants. The options may be chosen on the product page