The Siemens 6AV7611-0AB22-0BJ0 is a Panel PC belonging to the SIMATIC Panel PC 670 series, manufactured by Siemens. It is an industrial panel-mounted PC designed for demanding human-machine interface (HMI) and visualization tasks in automation environments. The unit integrates a flat-panel display with an embedded computing platform, providing a compact all-in-one solution for process visualization and control.
The SIMATIC Panel PC 670 (6AV7611-0AB22-0BJ0) features a 12-inch TFT display with a resolution of 800 x 600 pixels (SVGA) and supports touch screen operation. It is equipped with an Intel Celeron processor and runs Microsoft Windows XP or Windows CE depending on configuration, providing a familiar environment for SCADA and HMI software such as Siemens WinCC. The unit includes standard industrial interfaces including USB ports, Ethernet (RJ45), and serial COM ports, and is built to withstand industrial environments with a front panel protection rating of IP65. An integrated CompactFlash slot provides additional storage flexibility.
The SIMATIC Panel PC 670 is widely used in manufacturing, process automation, and machine tool industries where a robust, panel-integrated PC-based HMI is required. It is suitable for applications in automotive production lines, chemical processing plants, and packaging machinery where reliable visualization and operator interaction are critical. The fanless or low-noise design options make it appropriate for environments where maintenance access is limited and continuous operation is expected.
Technical Specifications
| Display Size | 12 inch |
|---|---|
| Display Resolution | 800 x 600 pixels (SVGA) |
| Display Type | TFT color LCD |
| Touch Technology | Resistive touch screen |
| Input Voltage | 24 V DC |
| Power Consumption | Approx. 60 W |
| Front Protection Rating | IP65 |
| Rear Protection Rating | IP20 |
| Communication Interface | Ethernet RJ45, USB, RS-232 (COM) |
| Storage | CompactFlash slot |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 5% to 90% (non-condensing) |
| Mounting | Panel mounting |
| Series/Product Family | SIMATIC Panel PC 670 |
| Certifications | CE, UL |
Common Error Codes & System Events
- Event ID: 100
- System startup error — the operating system failed to initialize correctly during boot.
Check CompactFlash card integrity and reseat it. Verify the OS image is intact. Restore or replace the CompactFlash card if corrupted. - Event ID: 200
- Watchdog timeout — the application software did not respond within the watchdog monitoring period.
Restart the HMI application. Check for software deadlocks or excessive CPU load. Update or reinstall the WinCC or HMI runtime software. - Event ID: 300
- Ethernet communication failure — loss of network connection detected.
Check Ethernet cable and switch connection. Verify IP address configuration. Inspect the RJ45 port for physical damage. - Event ID: 400
- Touch screen calibration error — touch input coordinates are misaligned or unresponsive.
Run the touch screen calibration utility from the Windows Control Panel or SIMATIC settings. Clean the touch surface and recalibrate. - Event ID: 500
- Power supply undervoltage — the 24 V DC supply voltage has dropped below the acceptable threshold.
Measure the supply voltage at the power connector. Ensure the supply is within the 24 V DC nominal range. Replace or adjust the power supply unit. - Event ID: 600
- CompactFlash read/write error — the system cannot access the CompactFlash storage device.
Reseat the CompactFlash card. Test the card in another reader. Replace the CompactFlash card if defective. - Event ID: 700
- Fan failure warning — cooling fan has stopped or is operating below minimum speed (if fan-cooled variant).
Inspect and clean the fan. Replace the fan module if it has failed. Ensure ventilation clearances around the unit are maintained. - Event ID: 800
- Internal temperature exceeded — the CPU or internal components have reached the thermal protection threshold.
Check ambient temperature and ensure it is within the 0–50 °C operating range. Clean air vents and verify fan operation. Reduce heat load or improve panel enclosure ventilation.
Frequently Asked Questions
What is the supply voltage for the 6AV7611-0AB22-0BJ0?
The unit operates on a 24 V DC supply voltage. Ensure the power source is stable and within the specified tolerance range.
What operating system does the SIMATIC Panel PC 670 (6AV7611-0AB22-0BJ0) run?
This Panel PC is designed to run Microsoft Windows XP Professional or Windows XP Embedded, depending on the ordered configuration. It supports Siemens WinCC and other PC-based HMI software.
What is the front panel protection rating of this unit?
The front panel of the 6AV7611-0AB22-0BJ0 carries an IP65 protection rating, making it resistant to dust and water jets, suitable for panel-flush installation in industrial enclosures.
What communication interfaces are available on this Panel PC?
The unit provides Ethernet (RJ45), USB ports, and RS-232 serial COM ports as standard interfaces, enabling connectivity to PLCs, networks, and peripheral devices.
Is the touch screen on the 6AV7611-0AB22-0BJ0 resistive or capacitive?
The touch screen uses resistive touch technology, which allows operation with gloved hands and is well-suited for industrial environments.
Troubleshooting
Display remains blank after power on
Check the 24 V DC supply voltage at the power connector using a multimeter. Verify that the power LED indicator is active. Inspect internal fuses if accessible.
Restore the correct 24 V DC supply. If the supply is correct and the display remains blank, the internal power supply board or display backlight inverter may be faulty and require replacement.
Touch screen does not respond or responds inaccurately
Determine whether the issue is a calibration problem or a hardware failure by observing if any touch input is registered at all. Check for physical damage or contamination on the touch surface.
Recalibrate the touch screen using the Windows calibration utility. Clean the screen surface. If unresponsive after recalibration, the touch controller board or touch overlay may need replacement.
Unit fails to boot or continuously restarts
Check the CompactFlash card for secure seating. Attempt to boot from an external source if possible. Listen for POST beep codes or observe any error messages on screen during startup.
Reseat or replace the CompactFlash card. Restore the OS image using a known-good backup. If the issue persists, the motherboard or processor module may be defective.
Ethernet communication is not established
Verify the Ethernet cable is connected and the link LED on the RJ45 port is active. Check IP address settings in Windows Network Connections. Test with a known-good cable and switch port.
Correct the IP configuration to match the network settings. Replace the Ethernet cable if faulty. If the link LED does not illuminate with a known-good cable, the onboard network adapter may be defective.
System reports high internal temperature or shuts down unexpectedly
Check the ambient temperature inside the panel enclosure. Inspect ventilation openings for blockages. If the unit has a fan, verify it is spinning correctly.
Reduce the ambient temperature by improving enclosure ventilation or adding cooling. Clean dust from vents and fan assemblies. Ensure the unit is installed with the minimum required clearances as specified in the hardware manual.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV3627-1QK00-2AX0 OP27
€ 749,00 – € 1.658,00Price range: € 749,00 through € 1.658,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177
€ 1.247,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6643-0AA01-1AX1 TP277
€ 249,00Select options This product has multiple variants. The options may be chosen on the product page