Siemens 6AV7264-3BM07-0AA0 SIMATIC IPC477C
€ 1.769,00
The Siemens 6AV7264-3BM07-0AA0 is an industrial panel PC belonging to the SIMATIC IPC477C series, manufactured by Siemens. It is a high-performance embedded panel PC designed for demanding HMI and SCADA applications in industrial environments. The unit integrates a flat-panel display with a built-in computing platform, offering a compact all-in-one solution for machine-level visualization and control tasks.
The IPC477C features a 15-inch TFT display with a resolution of 1024 x 768 pixels and resistive touch technology, enabling reliable operation even with gloved hands. It is powered by an Intel Core 2 Duo processor and supports Windows XP Professional or Windows Embedded Standard operating systems. The unit provides multiple communication interfaces including Ethernet (RJ45), USB ports, and serial interfaces, and is built to withstand industrial conditions with a fanless design option for reduced maintenance. The front panel meets IP65 protection rating, making it suitable for wash-down and dusty environments.
The SIMATIC IPC477C is widely used in the automotive, food and beverage, pharmaceutical, and machine tool industries where robust, long-lifecycle panel PCs are required. It integrates seamlessly with Siemens SIMATIC WinCC and other SCADA software platforms, making it a natural fit for Siemens-based automation architectures. Its industrial-grade construction and long-term availability of spare parts make it a preferred choice for OEMs and system integrators building machines with extended service lifetimes.
Technical Specifications
| Display Size | 15 inch |
|---|---|
| Display Resolution | 1024 x 768 pixels |
| Display Type | TFT LCD |
| Touch Technology | Resistive |
| Processor | Intel Core 2 Duo |
| Operating System | Windows XP Professional / Windows Embedded Standard |
| Input/Operating Voltage | 24 V DC |
| Front Panel Protection Rating | IP65 |
| Communication Interface | 2x Ethernet RJ45, 4x USB, 1x RS-232 |
| Mounting | Panel mounting |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 5% to 95% (non-condensing) |
| Certifications | CE, UL, cULus |
Common Error Codes & System Events
- Event ID: 1001
- Operating system startup failure or boot error detected during POST sequence.
Check storage medium (HDD/SSD/CF card) for errors. Verify OS installation integrity and replace storage medium if necessary. - Event ID: 1003
- Application error causing system crash or unexpected shutdown of the HMI runtime software.
Review Windows Event Viewer logs to identify the faulting application. Reinstall or update the HMI runtime software such as WinCC. - Event ID: 6008
- Unexpected system shutdown recorded, indicating a possible power loss or hardware fault.
Check 24 V DC supply voltage stability. Inspect power supply unit and all connectors for loose contacts or voltage drops. - Communication Error
- Loss of communication between the panel PC and the connected PLC or field devices.
Verify Ethernet cable connections and network switch status. Check IP address configuration and firewall settings on the IPC. - Watchdog Timeout
- Hardware watchdog timer has triggered due to system hang or unresponsive operating system.
Perform a controlled restart. If recurring, check CPU load, memory usage, and consider reinstalling the operating system. - Temperature Warning
- Internal temperature of the IPC has exceeded the defined threshold.
Check ambient temperature and ensure adequate ventilation or cooling around the unit. Clean any air vents or filters if present. - Storage Medium Error
- Read/write error detected on the internal hard disk, SSD, or CompactFlash card.
Run a disk diagnostic utility. Back up data immediately and replace the storage medium with a compatible unit. - Display Backlight Failure
- Display backlight has failed or brightness has dropped significantly, resulting in a dark or unreadable screen.
Replace the backlight unit or the display assembly. Check the backlight inverter board and associated connectors for damage.
Frequently Asked Questions
What is the supply voltage for the Siemens 6AV7264-3BM07-0AA0?
The SIMATIC IPC477C operates on a 24 V DC supply voltage, which is standard for Siemens industrial panel PCs.
What is the front panel protection rating of this panel PC?
The front panel of the 6AV7264-3BM07-0AA0 meets IP65 protection rating, providing protection against dust and water jets.
Is this panel PC compatible with Siemens WinCC SCADA software?
Yes, the SIMATIC IPC477C is fully compatible with Siemens SIMATIC WinCC and WinCC flexible HMI software, as it runs a Windows-based operating system.
What type of touch screen does this unit use?
The 6AV7264-3BM07-0AA0 uses resistive touch technology, which allows operation with gloved hands and is well-suited for industrial environments.
Can the storage medium be replaced or upgraded on this panel PC?
Yes, the internal storage medium such as the hard disk or CompactFlash card can be replaced. It is recommended to use Siemens-approved storage media to ensure compatibility and reliability.
Troubleshooting
Display remains blank after power on
Check the 24 V DC supply voltage at the power input connector. Verify that the power LED indicator is active. Measure backlight inverter output voltage.
Restore correct supply voltage if out of range. If supply is correct, replace the backlight inverter or display assembly. Check internal fuse if present.
Touch screen does not respond to input
Check if the operating system has fully booted and the HMI runtime is active. Test touch input in the Windows desktop environment to isolate hardware from software issues.
Recalibrate the touch screen using the Windows touch calibration utility. If unresponsive at hardware level, replace the touch screen overlay or the complete display assembly.
Panel PC fails to boot and shows POST error
Attempt to boot from an external USB device to determine if the internal storage medium has failed. Check BIOS settings for correct boot device order.
Replace the internal HDD, SSD, or CompactFlash card with a compatible unit and reinstall the operating system and HMI software.
Loss of communication with PLC over Ethernet
Verify physical Ethernet connection and check link LEDs on the RJ45 port. Use ping command to test network connectivity between the IPC and the PLC.
Replace Ethernet cable if faulty. Reconfigure IP address settings to match the network subnet. Check and update network adapter drivers if necessary.
System runs slowly or HMI runtime freezes intermittently
Monitor CPU and RAM usage via Windows Task Manager. Check for background processes consuming excessive resources. Verify that the storage medium is not failing using disk diagnostics.
Terminate unnecessary background processes or services. Increase virtual memory if RAM is insufficient. Replace the storage medium if disk errors are detected.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV3627-1NK00-2AX0 SIMATIC OP 27
€ 749,00 – € 964,00Price range: € 749,00 through € 964,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-8BA10-0AA0 TP177B
€ 964,00 – € 1.611,00Price range: € 964,00 through € 1.611,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AG1642-0BD01-2AX0 TP177B
€ 714,00Select options This product has multiple variants. The options may be chosen on the product page