• In-house repair workshop   ·   Emergency repairs   ·   New & used delivery   ·   Search & Rescue for end-of-life electronics
  • +31 513 201 218
    logo-smalllogo-smalllogo-smalllogo-small
    English
    • Dutch
    • German
    EMERGENCY REPAIR
    • Home
    • Products
      • Drive
      • HMI & Display
      • PLC
      • Power supply
      • Servo Motor
      • Products
    • Repair
      • Drives repair
        • Danfoss drives repair
        • Lenze drives repair
        • Schneider Eletric Altivar drives repair
        • Siemens Sinamics repair
      • HMI repair
        • Omron HMI repair
        • Siemens HMI repair
      • Custom repair
      • PCB repair
      • PLC-repair
      • Marine & offshore
    • Emergency repair
    • Search and Rescue
    • About us
      • Why Cirele
    • All brands
      • Allen-Bradley
      • Baumuller
      • Danfoss
      • Lenze
      • Omron
      • Schneider Electric
      • Siemens
      • Brands
    • News
    • Contact
    ✕
    • Home
    • HMI & Display
    • Siemens 6AV6645-0DE01-0AX0 SIMATIC MP 277
    Awaiting product image

    Siemens 6AV6645-0DE01-0AX0 SIMATIC MP 277

    € 1.770,00

    Reset
    Clear
    SKU: 6AV6645-0DE01-0AX0 Category: HMI & Display Brand: Siemens
    • Description
    • Additional information

    The Siemens 6AV6645-0DE01-0AX0 is a Multi Panel (MP 277) belonging to the SIMATIC HMI family, designed for machine-level visualization and operator control in industrial automation environments. This panel features a 10.4-inch TFT display and runs on the Windows CE operating system, providing a robust and flexible platform for human-machine interface applications. It is part of Siemens' established SIMATIC HMI panel portfolio, offering a balance of performance and versatility for mid-range automation tasks.

    The MP 277 10" Touch (6AV6645-0DE01-0AX0) is equipped with a resistive touchscreen interface and a 10.4-inch TFT display with a resolution of 640 x 480 pixels (VGA) supporting 256 colors. The panel includes 12 MB of user memory and communicates via PROFIBUS DP and MPI interfaces as standard, with an optional PROFINET/Ethernet interface available. It operates on a 24 V DC supply and supports connectivity through USB ports and a CompactFlash card slot for data storage and project transfer. The unit is rated IP65 on the front face, making it suitable for panel-mounting in environments where dust and water ingress protection is required.

    The SIMATIC MP 277 is widely used in manufacturing, automotive, food and beverage, and process industries where reliable operator panel visualization is required at the machine level. It is compatible with Siemens SIMATIC S7-300 and S7-400 PLCs, as well as third-party controllers via configurable communication drivers in WinCC flexible. Its combination of touch operation, robust construction, and broad communication support makes it a practical choice for machine builders and system integrators requiring a dependable mid-range HMI panel.

    Technical Specifications

    Display Size 10.4 inch
    Display Resolution 640 x 480 pixels (VGA)
    Display Colors 256 colors
    Display Type TFT LCD
    Touch Technology Resistive touchscreen
    Operating System Windows CE 5.0
    User Memory 12 MB
    Input/Operating Voltage 24 V DC
    Power Consumption Approx. 18 W
    Communication Interface PROFIBUS DP/MPI, USB (2x), Ethernet (optional)
    Storage CompactFlash card slot
    IP/Protection Rating IP65 (front), IP20 (rear)
    Operating Temperature 0 °C to +50 °C
    Storage Temperature -20 °C to +60 °C
    Relative Humidity 10% to 90% (non-condensing)
    Mounting Panel mounting
    Certifications CE, UL, cULus

    Common Error Codes & System Events

    Event ID: 10000
    Communication error between HMI panel and PLC. Connection to the configured controller cannot be established or has been lost.
    Check PROFIBUS/MPI or Ethernet cable connections and termination resistors. Verify PLC address settings match the HMI project configuration. Restart both PLC and HMI panel.
    Event ID: 10001
    Tag read error. The HMI panel cannot read a configured tag from the PLC.
    Verify the tag address in the WinCC flexible project matches the actual PLC data block or memory area. Check PLC program is running and the address exists.
    Event ID: 10002
    Tag write error. The HMI panel cannot write a value to a configured PLC tag.
    Check that the target PLC address is not write-protected. Verify the data type of the tag matches the PLC variable. Confirm the PLC is in RUN mode.
    Event ID: 20000
    Project download error. Transfer of the WinCC flexible project to the panel has failed.
    Ensure the panel is in Transfer mode. Check the communication cable or network connection between the engineering PC and the panel. Verify sufficient user memory is available on the panel.
    Event ID: 40000
    System memory low. Available runtime memory on the panel is critically low.
    Reduce the number of simultaneously active screens or objects. Optimize the WinCC flexible project by reducing image complexity and the number of active tags.
    Event ID: 70010
    Recipe data error. An error occurred during reading or writing of recipe data.
    Check the recipe configuration in WinCC flexible. Verify the CompactFlash card is properly inserted and not write-protected or corrupted. Reformat or replace the CompactFlash card if necessary.
    Event ID: 50000
    Alarm buffer overflow. The number of pending alarms has exceeded the buffer capacity of the panel.
    Acknowledge and clear existing alarms. Review the alarm configuration in WinCC flexible to reduce unnecessary alarm triggers. Increase alarm buffer size in project settings if possible.

    Frequently Asked Questions

    What PLC systems is the SIMATIC MP 277 compatible with?

    The MP 277 is primarily designed for use with Siemens SIMATIC S7-300 and S7-400 PLCs via MPI or PROFIBUS DP. It also supports communication with third-party controllers through configurable drivers available in WinCC flexible.

    What software is used to configure and program the MP 277?

    The MP 277 is configured using Siemens WinCC flexible 2008 or later. Projects are transferred to the panel via USB, Ethernet, or PROFIBUS connection from the engineering PC.

    What is the supply voltage for the 6AV6645-0DE01-0AX0?

    The panel requires a 24 V DC power supply. Ensure the supply is within the permitted tolerance range, typically 19.2 V DC to 28.8 V DC.

    Can the MP 277 be used with PROFINET?

    The base version of the MP 277 communicates via PROFIBUS DP and MPI. PROFINET/Ethernet communication is supported when the panel is equipped with the optional Ethernet interface or via the integrated Ethernet port on applicable variants.

    What type of memory card does the MP 277 use?

    The MP 277 uses a CompactFlash (CF) card for additional data storage, project backup, and firmware updates. The card is inserted into the dedicated slot on the rear of the panel.

    Troubleshooting

    Display remains blank after power is applied

    Check that 24 V DC is present at the power supply terminals on the rear of the panel. Measure voltage at the connector to confirm supply is within range. Inspect the internal fuse if accessible.

    Ensure the 24 V DC supply is stable and within tolerance (19.2–28.8 V DC). If voltage is correct and the display remains off, the backlight or internal power supply board may be faulty and require replacement.

    Touchscreen does not respond or responds inaccurately

    Determine whether the issue is a complete lack of response or positional inaccuracy. A miscalibrated touch panel will respond but in the wrong location. A completely unresponsive screen may indicate a hardware fault.

    Perform a touchscreen calibration via the Windows CE Control Panel or the Siemens Start Center on the panel. If calibration does not resolve the issue, the resistive touch overlay may be damaged and require replacement.

    HMI panel fails to communicate with the PLC

    Check the physical PROFIBUS or MPI cable connections and verify correct bus termination at both ends of the network. Confirm the PLC address and baud rate settings in the WinCC flexible project match the actual PLC configuration.

    Correct any address or baud rate mismatches in the project and reload it to the panel. Replace damaged cables or connectors. Ensure the PROFIBUS network has proper termination resistors enabled only at the two physical ends of the bus.

    Project transfer from PC to panel fails

    Verify the panel is set to Transfer mode via the Start Center. Check the USB or Ethernet connection between the engineering PC and the panel. Confirm the WinCC flexible version is compatible with the panel firmware version.

    Switch the panel to Transfer mode before initiating the download. Update the panel firmware if there is a version mismatch. Try an alternative transfer method (USB instead of Ethernet, or vice versa) to isolate the connection issue.

    Panel repeatedly restarts or crashes during operation

    Check for unstable 24 V DC power supply, particularly voltage dips under load. Review the WinCC flexible project for excessive script complexity or memory-intensive configurations that may overload the panel CPU.

    Stabilize the power supply and ensure adequate current capacity. Optimize the runtime project by reducing script complexity and the number of simultaneously active tags. If the problem persists, perform a factory reset and reload the project, or consider a firmware update.

    Condition

    Repair, Used, Refurbished, New in box (sealed)

    Related products

    • Siemens 6AG1545-0CC10-4AX0 SIPLUS HMI TP900

      Siemens 6AG1545-0CC10-4AX0 SIPLUS HMI TP900

      € 1.340,00
      Select options This product has multiple variants. The options may be chosen on the product page
    • Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177

      Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177

      € 1.247,00
      Select options This product has multiple variants. The options may be chosen on the product page
    • Siemens 6AV6642-0BC01-1AX0 TP177B

      Siemens 6AV6642-0BC01-1AX0 TP177B

      € 630,00 – € 1.421,00Price range: € 630,00 through € 1.421,00
      Select options This product has multiple variants. The options may be chosen on the product page

    Contact

    +31 513 201 218
    [email protected]

    CoC: 90417704
    VAT: NL865308317B01

    Location

    CirEle BV
    Röntgenweg 1
    8503 AG Joure
    The Netherlands

    General

    About us
    Shipping
    Terms and conditions
    Privacy policy
    Contact

    Repair

    Omron HMI repair
    Siemens HMI repair
    PLC repair
    Drives repair
    Request repair

    CirEle BV © 2026 | Terms and conditions | Privacy policy | Proudly powered by BOWI Marketing
      EMERGENCY REPAIR
      0

      € 0,00

      English
      • Dutch
      • English
      • German
        ✕

        Login

        Lost your password?

        Create an account?

        ✕

        Cart

        Proceed to checkout View cart
        • Shop
        • My account
        • 0 Cart