Siemens 6AV6542-0CC10-0AX0 TP177B
€ 1.244,00 – € 3.399,00Price range: € 1.244,00 through € 3.399,00
The Siemens 6AV6542-0CC10-0AX0 is a TP177B series touch panel HMI belonging to the SIMATIC HMI family, designed for machine-level visualization and operator control tasks. This unit features a 5.7-inch STN color display and operates as a compact, panel-mounted human-machine interface. It is part of the SIMATIC HMI Basic Panels generation and is manufactured by Siemens AG.
The TP177B 6AV6542-0CC10-0AX0 is equipped with a resistive touch screen and supports communication via MPI and PROFIBUS DP interfaces, enabling direct integration with SIMATIC S7-200, S7-300, and S7-400 PLCs. The panel runs the WinCC flexible runtime environment and offers 256 KB of user memory for project data. It supports configuration via WinCC flexible 2008 or later, and features a 320 x 240 pixel (QVGA) display resolution with 256 colors. The unit operates on a 24 V DC supply and is rated IP65 on the front panel for protection against dust and water ingress.
The TP177B is widely deployed in manufacturing automation, packaging machinery, conveyor systems, and process control applications where a compact, cost-effective HMI solution is required. Its PROFIBUS DP and MPI connectivity make it particularly suitable for integration into existing Siemens-based automation architectures. The panel is commonly found in industries such as food and beverage, automotive assembly, and general machine building.
Technical Specifications
| Display Size | 5.7 inch |
|---|---|
| Display Resolution | 320 x 240 px (QVGA) |
| Display Type | STN color |
| Display Colors | 256 colors |
| Touch Technology | Resistive touchscreen |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | 6 W (typical) |
| Communication Interface | MPI, PROFIBUS DP |
| User Memory | 256 KB |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| IP Rating (Front) | IP65 |
| IP Rating (Rear) | IP20 |
| Mounting | Panel mounting |
| Certifications | CE, UL, cULus |
| Series/Product Family | SIMATIC HMI TP177B |
Common Error Codes & System Events
- Event ID: 10000
- Communication error between HMI panel and PLC. The configured connection to the controller cannot be established or has been lost.
Check MPI or PROFIBUS DP cable connections and termination resistors. Verify PLC address settings match the HMI project configuration. Confirm the PLC is powered and in RUN mode. - Event ID: 10001
- Connection to the PLC was interrupted during runtime operation.
Inspect physical cabling for damage or loose connectors. Check bus termination and cable shielding. Restart both the HMI and PLC if the connection does not recover automatically. - Event ID: 20000
- Project download error. Transfer of the configuration project from the engineering PC to the HMI panel failed.
Ensure the HMI is in Transfer mode before initiating download. Verify the PC-to-panel cable (USB or MPI adapter) is correctly connected and the correct COM port is selected in WinCC flexible. - Event ID: 40000
- System memory low. Available runtime memory on the HMI panel is insufficient to load all configured screens or tags.
Reduce the number of active tags, screens, or graphical objects in the WinCC flexible project. Recompile and re-download the project to the panel. - Event ID: 50000
- Internal device error or hardware fault detected on the HMI panel.
Perform a panel restart. If the fault persists, back up the project and perform a factory reset via the Control Panel. Contact Siemens technical support if the error recurs after reset. - Event ID: 70000
- Configuration error detected. A tag or screen element references an address that does not exist in the connected PLC.
Open the WinCC flexible project and verify all tag addresses against the PLC data block or I/O configuration. Correct any invalid addresses and re-download the project. - Event ID: 30000
- Recipe data error. A recipe transfer to or from the PLC has failed or the recipe data is inconsistent.
Check that the recipe structure in the HMI project matches the corresponding data block in the PLC. Verify sufficient memory is available and re-initiate the recipe transfer.
Frequently Asked Questions
Which PLCs are compatible with the TP177B 6AV6542-0CC10-0AX0?
The TP177B is compatible with Siemens SIMATIC S7-200, S7-300, and S7-400 PLCs via MPI or PROFIBUS DP interfaces. It can also communicate with S7-200 via a dedicated PPI connection depending on configuration.
What software is required to configure this HMI panel?
The TP177B is configured using Siemens WinCC flexible 2008 or a compatible version. The project is then transferred to the panel via an MPI adapter or USB-to-MPI cable.
What is the supply voltage for the 6AV6542-0CC10-0AX0?
The panel requires a 24 V DC power supply. Ensure the supply is within the permissible tolerance range as specified in the Siemens TP177B operating instructions.
What is the front panel protection rating of this unit?
The front panel of the TP177B 6AV6542-0CC10-0AX0 is rated IP65, providing full protection against dust ingress and protection against low-pressure water jets. The rear of the unit is rated IP20.
Can the TP177B be used as a replacement for older Siemens OP/TP panels?
The TP177B can serve as a functional replacement for older SIMATIC HMI panels such as the TP170B in many applications, provided the WinCC flexible project is adapted to the new hardware configuration and communication settings are updated accordingly.
Troubleshooting
Display remains blank after power is applied
Measure the 24 V DC supply voltage at the power connector on the rear of the panel. Check for correct polarity. Inspect the internal fuse if accessible.
Ensure the power supply is within the 24 V DC tolerance range and correctly wired. If the supply is confirmed good and the display remains blank, the backlight or internal power board may be faulty and the unit should be sent for repair or replacement.
HMI shows 'No connection to PLC' or communication error at runtime
Verify the MPI or PROFIBUS DP cable is securely connected at both the HMI and PLC ends. Check bus termination resistors are correctly placed at both ends of the bus segment. Confirm the PLC station address in the HMI project matches the actual PLC address.
Replace or reseat the communication cable. Correct the bus termination. Update the PLC address in the WinCC flexible project and re-download to the panel. If using an MPI network, ensure no address conflicts exist on the bus.
Touchscreen does not respond or registers incorrect touch positions
Attempt to recalibrate the touchscreen via the Siemens Control Panel accessible during startup (press and hold the touch area during boot to enter the loader menu). Check for physical damage or contamination on the screen surface.
Perform a touchscreen recalibration from the Control Panel settings. Clean the screen surface with a soft, dry cloth. If calibration does not resolve the issue, the resistive touch overlay may be worn or damaged and requires replacement.
Project transfer from PC to HMI panel fails
Confirm the HMI is in Transfer mode (accessible via the loader menu on startup). Check the MPI adapter or PC adapter cable connection and verify the correct interface and baud rate are selected in WinCC flexible transfer settings.
Set the panel to Transfer mode before initiating the download. Ensure the correct COM port and transfer rate are configured in WinCC flexible. Try a different MPI adapter or cable if the issue persists. Verify the PC has the correct driver installed for the MPI adapter.
Panel repeatedly restarts or enters a boot loop
Check the 24 V DC supply for voltage drops or instability under load. Inspect the project file for corruption by attempting to load a minimal test project. Check if the panel enters the loader menu successfully before the restart occurs.
Stabilize the power supply and ensure adequate current capacity. Perform a factory reset via the loader menu to clear potentially corrupted runtime data. Re-download a freshly compiled project from WinCC flexible. If the boot loop continues after reset, the panel hardware may require servicing.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV6642-0BC01-1AX1 TP177B
€ 657,00 – € 1.249,00Price range: € 657,00 through € 1.249,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1NK00-0AX0 SIMATIC OP 27
€ 755,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6545-8CC10-0AA0 Mobile Panel 177
€ 1.247,00Select options This product has multiple variants. The options may be chosen on the product page