Siemens 6AV7611-0AE32-0BJ0 SIMATIC Panel PC 670
€ 1.770,00
The Siemens 6AV7611-0AE32-0BJ0 is a Panel PC belonging to the SIMATIC Panel PC 670 series, manufactured by Siemens. It is an industrial panel-mounted PC designed for demanding human-machine interface (HMI) and visualization tasks in automation environments. The unit integrates computing hardware and a display into a single ruggedized enclosure suitable for direct panel mounting.
The SIMATIC Panel PC 670 features a 12-inch TFT color display with a resolution of 800 x 600 pixels (SVGA), and is equipped with a resistive touchscreen for operator input. It runs on a Celeron or Pentium M class processor platform and supports Windows XP Professional or Windows XP Embedded as the operating system. The unit provides multiple communication interfaces including Ethernet (RJ45), USB ports, and serial interfaces (RS-232/RS-422/RS-485), enabling integration with a wide range of Siemens and third-party automation systems. It is designed for fanless or low-noise operation with an IP65-rated front panel for protection against dust and water ingress.
The SIMATIC Panel PC 670 is widely used in manufacturing, process automation, and machine tool industries where a robust, panel-integrated PC solution is required. Its compatibility with standard Windows-based SCADA and HMI software such as Siemens WinCC makes it suitable for complex visualization and data acquisition tasks. The IP65 front protection and wide operating temperature range make it appropriate for installation in industrial control cabinets and harsh production environments.
Technical Specifications
| Display Size | 12 inch |
|---|---|
| Display Resolution | 800 x 600 pixels (SVGA) |
| Display Type | TFT Color LCD |
| Touch Technology | Resistive Touchscreen |
| Front Panel Protection | IP65 |
| Input Voltage | 24 V DC |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 5% to 90% (non-condensing) |
| Communication Interfaces | Ethernet (RJ45), USB, RS-232, RS-422/RS-485 |
| Operating System | Windows XP Professional / Windows XP Embedded |
| Mounting | Panel Mounting |
| Series | SIMATIC Panel PC 670 |
| Certifications | CE, UL |
Common Error Codes & System Events
- Event ID: 100
- System startup error — the operating system failed to load correctly during boot.
Check the Compact Flash card or hard disk for integrity. Reinstall or restore the operating system image using the Siemens recovery tools. - Event ID: 1000
- Application fault — a software application has crashed or become unresponsive.
Restart the affected application. Check Windows Event Viewer for detailed error logs and update or reinstall the HMI software if the fault recurs. - Event ID: 7026
- Driver load failure — a hardware driver failed to load during system startup.
Check Device Manager for driver conflicts. Reinstall the appropriate driver from the Siemens Panel PC driver package. - Event ID: 6008
- Unexpected shutdown — the system was shut down unexpectedly, possibly due to a power interruption.
Verify the 24 V DC power supply stability. Check all power connectors and ensure the supply voltage is within the specified range. - BIOS POST Error
- Hardware self-test failure detected during Power-On Self-Test (POST).
Check that all internal modules (RAM, storage) are properly seated. If the error persists, replace the faulty hardware module or contact Siemens service. - Watchdog Timeout
- The system watchdog timer has expired, indicating the operating system or application has stopped responding.
Investigate software processes causing the hang. Ensure the HMI application is correctly configured and that system resources are not exhausted. - Touch Controller Error
- The resistive touchscreen controller is not responding or has lost calibration.
Recalibrate the touchscreen using the Siemens calibration utility in the control panel. If unresponsive, check the internal touch controller connection or replace the touchscreen assembly.
Frequently Asked Questions
What is the supply voltage for the SIMATIC Panel PC 670 (6AV7611-0AE32-0BJ0)?
The unit operates on a 24 V DC supply voltage. Ensure the power supply is stable and within the specified tolerance range.
What operating system does the 6AV7611-0AE32-0BJ0 support?
This Panel PC supports Windows XP Professional and Windows XP Embedded. It is not natively compatible with Windows 10 or later without hardware upgrades.
Is the 6AV7611-0AE32-0BJ0 compatible with Siemens WinCC?
Yes, the SIMATIC Panel PC 670 is compatible with Siemens WinCC and other Windows-based HMI and SCADA software packages.
What is the front panel protection rating of this unit?
The front panel of the 6AV7611-0AE32-0BJ0 is rated IP65, providing protection against dust and low-pressure water jets.
What communication interfaces are available on this Panel PC?
The unit provides Ethernet (RJ45), USB ports, and serial interfaces (RS-232 and RS-422/RS-485) for connectivity to PLCs, drives, and other automation devices.
Troubleshooting
Display remains blank after power on
Check the 24 V DC supply voltage at the power connector. Verify that the power LED is illuminated. Measure voltage at the internal power supply output.
Ensure the supply voltage is within the 24 V DC specification. If the internal power supply has failed, replace the power supply module. If the display backlight has failed, replace the backlight or the display assembly.
Touchscreen does not respond to input
Attempt to operate the system using a connected USB mouse or keyboard to determine if the issue is isolated to the touchscreen. Check Device Manager for touchscreen controller errors.
Recalibrate the touchscreen via the Siemens calibration utility. If the controller is not detected, check the internal ribbon cable connection. Replace the touchscreen assembly if the hardware is faulty.
System fails to boot or repeatedly restarts
Observe the boot sequence for BIOS POST errors. Check the Compact Flash card or hard disk for physical damage or corruption using diagnostic tools.
Restore the operating system using the Siemens recovery image. Replace the Compact Flash card or storage device if it is found to be defective.
Ethernet communication not established
Check the Ethernet cable and switch port. Verify the IP address configuration in Windows Network Settings. Check Device Manager for network adapter errors.
Reconfigure the IP address settings to match the network requirements. Update or reinstall the network adapter driver from the Siemens driver package. Replace the Ethernet cable if damaged.
System runs slowly or HMI application freezes
Check CPU and memory usage in Windows Task Manager. Identify any background processes consuming excessive resources. Check available storage space on the system drive.
Close unnecessary background applications. Free up storage space on the system drive. If the issue persists, consider restoring the system to a clean OS image using the Siemens recovery tools.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AG1642-0BA01-4AX1 TP177B
€ 1.040,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-0BC01-1AX0 TP177B
€ 630,00 – € 1.421,00Price range: € 630,00 through € 1.421,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1QK00-2AX0 OP27
€ 749,00 – € 1.658,00Price range: € 749,00 through € 1.658,00Select options This product has multiple variants. The options may be chosen on the product page