Siemens 6AV7250-3GC07-0HA0 SIMATIC IPC277D
€ 1.567,00
The Siemens 6AV7250-3GC07-0HA0 is a panel PC belonging to the SIMATIC IPC277D series, part of Siemens' industrial-grade embedded panel PC lineup. It is designed for demanding human-machine interface applications requiring a robust, fanless computing platform integrated with a touchscreen display. This unit combines the functionality of an industrial PC with a flat-panel operator interface in a single compact enclosure.
The IPC277D features a widescreen multi-touch display with a resistive or projected capacitive touch interface, depending on the variant, and is built around an Intel Atom processor platform for reliable embedded operation. It supports communication via standard interfaces including USB, Ethernet (RJ45), and serial ports, and is compatible with PROFINET for integration into Siemens automation networks. The unit runs Windows Embedded Standard 7 or Windows 7 Professional, supports onboard flash or SSD storage, and is rated for continuous industrial operation with an IP65 front panel protection rating. The fanless design eliminates moving parts, reducing maintenance requirements and extending service life.
The SIMATIC IPC277D is widely deployed in manufacturing automation, process control, and machine tool applications where a compact, panel-mount HMI with PC functionality is required. It is commonly used in conjunction with Siemens SIMATIC S7 PLCs and TIA Portal engineering software, making it suitable for industries such as automotive, food and beverage, pharmaceuticals, and general factory automation. Its rugged construction and wide operating temperature range make it appropriate for installation in control cabinets and machine panels in industrial environments.
Technical Specifications
| Series | SIMATIC IPC277D |
|---|---|
| Display Size | 15 inch |
| Touch Technology | Resistive touchscreen |
| Processor | Intel Atom E3827 (dual-core) |
| Operating System | Windows 7 Professional or Windows Embedded Standard 7 |
| Storage | Onboard CFast or SSD |
| Communication Interface | 2x RJ45 Ethernet (PROFINET), 4x USB 2.0, 1x RS-232/422/485 |
| IP Protection Rating (Front) | IP65 |
| IP Protection Rating (Rear) | IP20 |
| Input Voltage | 24 V DC |
| Power Consumption | Approx. 40 W |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 5 % to 90 % (non-condensing) |
| Mounting | Panel mount (flush mounting) |
| Certifications | CE, UL, cULus |
Common Error Codes & System Events
- Event ID: 100
- Operating system startup failure or boot error detected during POST.
Check storage medium (CFast/SSD) for integrity. Re-seat or replace the storage device. Restore OS image if corrupted. - Event ID: 200
- Overtemperature condition detected on the processor or system board.
Check ambient temperature and ventilation around the panel. Clean any dust from ventilation areas. Verify the panel cutout dimensions allow adequate airflow. - Event ID: 300
- Ethernet/PROFINET communication link failure.
Check RJ45 cable connections and network switch status. Verify IP address configuration in Windows Device Manager. Replace cable or check network infrastructure. - Event ID: 400
- USB device not recognized or USB port fault.
Disconnect and reconnect the USB device. Test with a known-good USB device. Check for driver conflicts in Windows Device Manager. - Event ID: 500
- Touchscreen calibration error or touch input not responding.
Recalibrate the touchscreen via the Siemens Touchscreen Calibration tool in the Control Panel. If unresponsive, check the internal touch controller ribbon cable connection. - Event ID: 600
- Power supply undervoltage detected; supply voltage below permissible range.
Measure the 24 V DC supply at the power connector. Ensure supply voltage is within the 20.4–28.8 V DC tolerance range. Replace or adjust the power supply unit. - Event ID: 700
- BIOS/firmware configuration error or CMOS battery failure.
Replace the internal CMOS battery (CR2032 type). Re-enter BIOS settings and save correct configuration. Update BIOS firmware if required via Siemens support.
Frequently Asked Questions
What operating systems are supported on the SIMATIC IPC277D (6AV7250-3GC07-0HA0)?
The IPC277D supports Windows 7 Professional and Windows Embedded Standard 7. The specific OS variant depends on the order configuration of the unit.
What is the supply voltage for this panel PC?
The 6AV7250-3GC07-0HA0 operates on a 24 V DC supply, with a permissible voltage range of approximately 20.4 V DC to 28.8 V DC.
Is the SIMATIC IPC277D compatible with Siemens TIA Portal and WinCC?
Yes, the IPC277D is fully compatible with Siemens TIA Portal and can run WinCC Runtime software, making it suitable for use as an operator station in SIMATIC automation systems.
What is the front panel protection rating of this unit?
The front panel of the IPC277D is rated IP65, providing protection against dust ingress and low-pressure water jets, making it suitable for panel-mount installation in industrial environments.
Can the storage medium be replaced or upgraded in the field?
Yes, the CFast card or SSD used as the storage medium is accessible and can be replaced in the field. Siemens provides recovery images to restore the operating system after storage replacement.
Troubleshooting
Display remains blank after power is applied
Measure the 24 V DC supply voltage at the power connector. Check that the voltage is within the 20.4–28.8 V DC range. Inspect the internal fuse and power supply board for signs of failure.
Correct the supply voltage if out of range. Replace the internal fuse if blown. If the power supply board is faulty, replace the internal power supply module or return the unit for repair.
Touchscreen does not respond to touch input
Verify that the touchscreen driver is correctly installed in Windows Device Manager. Check the internal ribbon cable connecting the touch controller to the mainboard for damage or loose connection.
Reinstall or update the touchscreen driver from the Siemens support portal. Re-seat the internal ribbon cable. If the touch controller is defective, replace the front panel assembly.
Unit fails to boot and shows a black screen with BIOS error
Check whether the CFast card or SSD is properly seated. Attempt to boot from an external USB recovery drive. Inspect BIOS settings for incorrect boot order configuration.
Re-seat the storage medium. Restore the OS image using the Siemens recovery USB tool. If the CMOS battery is flat, replace it (CR2032) and reconfigure BIOS settings.
PROFINET or Ethernet communication is not established
Check the RJ45 cable and verify link LEDs on the Ethernet port are active. Confirm the IP address configuration in Windows matches the network settings. Check for driver issues in Device Manager.
Replace the Ethernet cable if damaged. Reconfigure the IP address settings. Reinstall the network adapter driver from the Siemens support portal if the adapter is not recognized.
System runs slowly or freezes during operation
Check CPU and memory utilization in Windows Task Manager. Verify that the operating temperature is within specification. Check the storage medium for errors using Windows disk diagnostics.
Close unnecessary background applications and services. Ensure ambient temperature is within 0–50 °C. Replace the CFast card or SSD if storage errors are detected, and restore the OS image.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV3627-1NK00-2AX0 SIMATIC OP 27
€ 749,00 – € 964,00Price range: € 749,00 through € 964,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AG1545-0BC15-2AX0 SIPLUS HMI TP900
€ 875,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-8BA10-0AA0 TP177B
€ 964,00 – € 1.611,00Price range: € 964,00 through € 1.611,00Select options This product has multiple variants. The options may be chosen on the product page