• In-house repair workshop   ·   Emergency repairs   ·   New & used delivery   ·   Search & Rescue for end-of-life electronics
  • +31 513 201 218
    logo-smalllogo-smalllogo-smalllogo-small
    English
    • Dutch
    • German
    EMERGENCY REPAIR
    • Home
    • Products
      • Drive
      • HMI & Display
      • PLC
      • Power supply
      • Servo Motor
      • Products
    • Repair
      • Drives repair
        • Danfoss drives repair
        • Lenze drives repair
        • Schneider Eletric Altivar drives repair
        • Siemens Sinamics repair
      • HMI repair
        • Omron HMI repair
        • Siemens HMI repair
      • Custom repair
      • PCB repair
      • PLC-repair
      • Marine & offshore
    • Emergency repair
    • Search and Rescue
    • About us
      • Why Cirele
    • All brands
      • Allen-Bradley
      • Baumuller
      • Danfoss
      • Lenze
      • Omron
      • Schneider Electric
      • Siemens
      • Brands
    • News
    • Contact
    ✕
    • Home
    • PLC
    • Siemens 3TK2821-1CB30 SIRIUS 3TK2821
    Awaiting product image

    Siemens 3TK2821-1CB30 SIRIUS 3TK2821

    Reset

    This product is currently out of stock and unavailable.

    SKU: 3TK2821-1CB30 Category: PLC Brand: Siemens
    • Description
    • Additional information

    The Siemens SIRIUS 3TK2821-1CB30 is a safety relay module belonging to the SIRIUS 3TK28 series, manufactured by Siemens AG. It is designed to monitor safety-critical functions such as emergency stop circuits, safety door interlocks, and two-hand control devices in industrial automation systems. The module provides reliable safety switching and is compliant with international functional safety standards.

    The 3TK2821-1CB30 operates on a 24 V DC coil voltage and provides two safety-rated enabling current paths along with one auxiliary contact for signaling purposes. It achieves up to Safety Integrity Level SIL 3 per IEC 62061 and Performance Level PL e per ISO 13849-1, making it suitable for the highest safety categories. The module features guided (positively driven) contacts, automatic or manual reset options, and a compact 22.5 mm wide housing designed for DIN rail mounting.

    This safety relay is widely used in machinery and plant engineering wherever personnel protection is required, including press and stamping machines, packaging lines, robotic cells, and conveyor systems. Its compact footprint and straightforward wiring make it suitable for integration into existing control cabinets across automotive, food and beverage, and general manufacturing industries.

    Technical Specifications

    Series SIRIUS 3TK28
    Input/Operating Voltage 24 V DC
    Safety Integrity Level SIL 3 (IEC 62061)
    Performance Level PL e (ISO 13849-1)
    Safety Category Category 4 (EN ISO 13849-1)
    Enabling Current Paths 2 (safety contacts, N/O)
    Auxiliary Contacts 1 N/C (signaling)
    Rated Operational Voltage 250 V AC / 24 V DC
    Rated Operational Current 6 A (AC-15), 6 A (DC-13)
    Reset Type Automatic or manual (selectable)
    Mounting DIN rail (35 mm)
    Housing Width 22.5 mm
    Operating Temperature -25 °C to +60 °C
    Protection Rating IP40 (front), IP20 (terminals)
    Certifications CE, UL, cUL, TÜV

    Common Diagnostic Codes

    LED OFF (no indication)
    The safety relay is de-energized or supply voltage is absent.
    Check 24 V DC supply voltage at the input terminals. Verify wiring connections and fuse integrity in the control circuit.
    LED flashing (input circuit fault)
    The input monitoring circuit has detected a discrepancy or short-circuit across the safety input channels.
    Inspect the emergency stop button or safety door switch wiring for cross-faults or short circuits. Ensure both input channels are correctly wired and the safety device is functioning.
    Output contacts not closing
    The enabling contacts do not close after the reset signal is applied.
    Verify that the reset input is correctly wired and that the reset button is being pressed after the safety circuit is restored. Check for welded contacts on the feedback loop (EDM) circuit.
    Feedback loop (EDM) fault
    The external device monitoring (EDM) circuit has detected that downstream contactors or relays have not de-energized correctly.
    Check the auxiliary contacts of downstream contactors wired into the EDM/feedback loop. Replace any welded or stuck contactors and verify correct wiring of the feedback circuit.
    Output contacts welded
    One or more safety output contacts are welded closed due to overcurrent or short circuit.
    Replace the 3TK2821 safety relay module. Investigate the cause of overcurrent in the load circuit and install appropriate fusing or protection.
    Reset not effective
    The relay does not reset after the safety circuit is re-established and reset button is pressed.
    Check that the safety input circuit is fully closed (emergency stop released, door closed). Verify reset wiring and confirm manual reset mode is correctly configured. Inspect for residual faults in the input circuit.

    Frequently Asked Questions

    What is the coil supply voltage for the 3TK2821-1CB30?

    The 3TK2821-1CB30 is designed for a 24 V DC supply voltage on the control input circuit.

    What safety level does the 3TK2821-1CB30 achieve?

    The module achieves Safety Integrity Level SIL 3 per IEC 62061 and Performance Level PL e per ISO 13849-1, Category 4.

    Does the 3TK2821-1CB30 support both automatic and manual reset?

    Yes, the reset mode can be configured for either automatic or monitored manual reset depending on the application requirements.

    How many safety output contacts does the 3TK2821-1CB30 provide?

    The module provides two N/O safety enabling contacts and one N/C auxiliary signaling contact.

    Is the 3TK2821-1CB30 compatible with two-channel emergency stop circuits?

    Yes, the 3TK2821 series is designed to monitor two-channel emergency stop devices, safety door switches, and two-hand control devices in accordance with relevant machinery safety standards.

    Troubleshooting

    Safety relay does not energize after power is applied

    Check the 24 V DC supply voltage at the A1/A2 terminals using a multimeter. Verify that the supply is within tolerance and that no fuse has blown in the control circuit.

    Restore correct 24 V DC supply voltage. Replace any blown fuses and correct wiring errors at the supply terminals.

    Enabling output contacts do not close after reset

    Confirm that the safety input circuit (e.g., emergency stop) is fully re-established and that the reset button is being pressed. Check the EDM feedback loop for welded downstream contacts.

    Release and re-engage the safety device, then press the reset button. If the EDM loop is open due to welded contacts on a downstream contactor, replace the faulty contactor and rewire the feedback circuit correctly.

    Safety relay trips unexpectedly during operation

    Inspect the safety input wiring for loose connections, intermittent contact faults, or electromagnetic interference causing spurious signals on the input channels.

    Tighten all terminal connections, use shielded cables where appropriate, and ensure the safety input device (e.g., E-stop button) contacts are in good condition. Replace worn safety devices if necessary.

    Auxiliary signaling contact does not change state

    Measure continuity across the auxiliary N/C contact terminals when the relay is energized. A failed auxiliary contact or incorrect wiring may be the cause.

    Verify wiring to the auxiliary contact terminals. If the contact is confirmed faulty, replace the 3TK2821 module as the contacts are not field-repairable.

    Module shows signs of overheating or discoloration

    Check the load current through the safety output contacts against the rated operational current. Verify that the ambient temperature inside the cabinet does not exceed 60 °C.

    Reduce the load current to within rated limits, improve cabinet ventilation, and replace the module if thermal damage is evident. Install appropriately rated fusing upstream of the safety contacts.

    Condition

    Repair, Used, Refurbished, New in box (sealed)

    Related products

    • Placeholder

      Siemens 6ES5955-3LF12 SIMATIC S5 955

      € 69,00 – € 624,00Price range: € 69,00 through € 624,00
      Select options This product has multiple variants. The options may be chosen on the product page
    • Placeholder

      Sold out

      Siemens Simatic S7 6GK7343-5FA01-0XE0

      Read more
    • Placeholder

      Siemens Simatic ET200 6ES7131-1BH11-0XB0

      € 267,00
      Select options This product has multiple variants. The options may be chosen on the product page

    Contact

    +31 513 201 218
    [email protected]

    CoC: 90417704
    VAT: NL865308317B01

    Location

    CirEle BV
    Röntgenweg 1
    8503 AG Joure
    The Netherlands

    General

    About us
    Shipping
    Terms and conditions
    Privacy policy
    Contact

    Repair

    Omron HMI repair
    Siemens HMI repair
    PLC repair
    Drives repair
    Request repair

    CirEle BV © 2026 | Terms and conditions | Privacy policy | Proudly powered by BOWI Marketing
      EMERGENCY REPAIR
      0

      € 0,00

      English
      • Dutch
      • English
      • German
        ✕

        Login

        Lost your password?

        Create an account?

        ✕

        Cart

        Proceed to checkout View cart
        • Shop
        • My account
        • 0 Cart