Siemens 6AV7611-0AA10-0BF0 SIMATIC Panel PC 670
€ 1.770,00
The Siemens 6AV7611-0AA10-0BF0 is a Panel PC belonging to the SIMATIC Panel PC 670 series, manufactured by Siemens. It is an industrial-grade panel computer designed for demanding human-machine interface (HMI) and visualization tasks in automation environments. This unit integrates a flat-panel display with a full PC platform, offering a compact and robust solution for machine-level and process-level control visualization.
The SIMATIC Panel PC 670 features a 15-inch TFT display with a resolution of 1024 x 768 pixels (XGA) and supports touch screen operation. It is built around an industrial PC architecture running a Windows-based operating system, and is equipped with interfaces including USB, Ethernet (RJ45), and serial COM ports for connectivity to PLCs and peripheral devices. The unit is designed for front-panel mounting with an IP65-rated front bezel, providing protection against dust and water ingress in industrial environments. It supports SIMATIC WinCC and other Siemens HMI software platforms for visualization and SCADA applications.
The SIMATIC Panel PC 670 is widely used in manufacturing, automotive, chemical processing, and energy industries where a full PC-based HMI platform is required at the machine or control cabinet level. Its rugged construction and industrial-grade components make it suitable for continuous operation in environments with vibration, temperature variation, and electromagnetic interference. The integration of standard PC interfaces allows easy connection to existing plant networks and enterprise systems.
Technical Specifications
| Display Size | 15 inch |
|---|---|
| Display Resolution | 1024 x 768 pixels (XGA) |
| Display Type | TFT color LCD |
| Touch Technology | Resistive touchscreen |
| Input Voltage | 24 V DC |
| Power Consumption | Approx. 60 W |
| IP Rating (Front) | IP65 |
| IP Rating (Rear) | IP20 |
| Operating Temperature | 0 °C to +45 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 5% to 90% (non-condensing) |
| Communication Interface | Ethernet RJ45, USB, RS-232 (COM) |
| Mounting | Front panel mounting |
| Certifications | CE, UL |
| Series/Product Family | SIMATIC Panel PC 670 |
Common Error Codes & System Events
- Event ID: 100
- Operating system startup failure or boot error detected during POST sequence.
Check hard disk or CompactFlash card integrity. Verify BIOS settings and reseat storage media. Replace storage device if corrupted. - Event ID: 200
- Touchscreen calibration error or touch input not responding correctly.
Recalibrate the touchscreen via the Windows control panel or SIMATIC touchscreen calibration utility. If persistent, check touchscreen controller connection internally. - Event ID: 300
- Ethernet communication link failure or network interface not detected.
Check Ethernet cable and network switch connection. Verify IP configuration in Windows network settings. Replace Ethernet cable or check RJ45 port for damage. - Event ID: 400
- Internal temperature warning — operating temperature threshold exceeded.
Check ambient temperature around the panel. Ensure ventilation slots are not blocked. Verify cooling fan operation if equipped. Reduce ambient temperature or improve cabinet ventilation. - Event ID: 500
- Power supply undervoltage detected on 24 V DC input.
Measure the 24 V DC supply at the power input connector. Ensure supply voltage is within 20.4–28.8 V DC range. Check wiring and power supply unit output. - Event ID: 600
- WinCC Runtime communication error — connection to PLC lost.
Verify PLC connection parameters in WinCC project. Check Ethernet or MPI/PROFIBUS cable connections. Restart WinCC Runtime and confirm PLC is in RUN mode. - Event ID: 700
- Hard disk or storage media failure warning reported by operating system.
Back up project data immediately. Run disk diagnostics using Windows tools. Replace the hard disk or CompactFlash storage module as required.
Frequently Asked Questions
What operating system does the SIMATIC Panel PC 670 (6AV7611-0AA10-0BF0) run?
The SIMATIC Panel PC 670 is typically supplied with Windows XP Professional or Windows 2000 Professional as the operating system, depending on the specific order configuration. This variant (0BF0) is associated with a Windows XP-based configuration.
What HMI software is compatible with this Panel PC?
The Panel PC 670 is compatible with Siemens SIMATIC WinCC, WinCC flexible Runtime, and ProTool/Pro Runtime software. It can also run third-party SCADA and visualization software compatible with the Windows operating system.
What is the input voltage requirement for the 6AV7611-0AA10-0BF0?
The unit requires a 24 V DC power supply. The acceptable input voltage range is typically 20.4 V DC to 28.8 V DC.
Is the front panel of this unit protected against dust and water?
Yes, the front panel of the SIMATIC Panel PC 670 carries an IP65 protection rating, making it resistant to dust ingress and low-pressure water jets. The rear of the unit is rated IP20.
What communication interfaces are available on this Panel PC?
The 6AV7611-0AA10-0BF0 provides Ethernet (RJ45), USB ports, and RS-232 serial COM ports. Additional interfaces such as MPI/PROFIBUS may be available via expansion cards depending on the configuration.
Troubleshooting
Display remains blank after power is applied
Check that the 24 V DC supply voltage is present at the power input connector using a multimeter. Verify the supply is within the 20.4–28.8 V DC range. Check internal fuse and power supply board.
Restore correct supply voltage if out of range. Replace the internal fuse if blown. If the backlight is faulty, the backlight inverter or LCD panel assembly may need replacement.
Touchscreen does not respond or registers incorrect touch positions
Attempt to recalibrate the touchscreen using the Windows control panel or SIMATIC calibration tool. Check for physical damage or contamination on the touch surface.
Perform a full touchscreen recalibration. Clean the touch surface with a soft cloth. If recalibration fails, the resistive touchscreen overlay or its controller board may need replacement.
Panel PC fails to boot or shows operating system errors on startup
Check the hard disk or CompactFlash storage device for errors using Windows recovery tools or an external diagnostic tool. Listen for unusual hard disk noises indicating mechanical failure.
Run a disk check and repair corrupted system files. If the storage media has failed, replace the hard disk or CompactFlash card and reinstall the operating system and WinCC project.
Loss of communication between Panel PC and PLC
Verify the Ethernet or serial cable connection between the Panel PC and the PLC. Check the WinCC or ProTool communication channel configuration for correct IP address, MPI address, or COM port settings.
Replace or reseat the communication cable. Correct any misconfigured communication parameters in the HMI project. Ensure the PLC is powered and in RUN mode. Restart WinCC Runtime after correcting settings.
Unit overheating or shutting down unexpectedly during operation
Check the ambient temperature around the panel and verify that ventilation openings on the enclosure are not obstructed. Monitor the CPU temperature via Windows system tools if accessible.
Improve airflow around the panel by clearing obstructions. If the unit has an internal cooling fan, inspect and replace it if it has failed. Ensure the panel is not installed in an environment exceeding the 45 °C maximum operating temperature.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV6642-0BC01-1AX1 TP177B
€ 657,00 – € 1.249,00Price range: € 657,00 through € 1.249,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-5AA00-0QE0 TP177B
€ 394,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-0BA01-1AX1 TP177B
€ 723,00 – € 2.499,00Price range: € 723,00 through € 2.499,00Select options This product has multiple variants. The options may be chosen on the product page