Siemens 6AV6355-1AA47-7CJ4 OP 177B
€ 3.495,00
The Siemens 6AV6355-1AA47-7CJ4 is an operator panel belonging to the SIMATIC OP 177B series, part of Siemens' established line of operator panels for industrial human-machine interface applications. This unit provides a monochrome or color graphical display interface designed for use with Siemens SIMATIC controllers and compatible third-party systems. The OP 177B series is engineered for demanding industrial environments where reliable operator interaction and process visualization are required.
The OP 177B panel features a 5.7-inch STN display with a resolution of 320 x 240 pixels and supports both touch and key-based operation, combining a resistive touchscreen with a membrane keypad for flexible input methods. It includes MPI/PROFIBUS DP and RS-422/RS-485 communication interfaces, enabling direct integration with S7-200, S7-300, and S7-400 PLCs. The panel is configured using WinCC flexible engineering software and supports recipe management, alarm logging, and trend display functions. It operates on a 24 V DC supply and is rated IP65 on the front face for protection against dust and water ingress.
The OP 177B is widely deployed in machine automation, conveyor systems, packaging machinery, and process control panels across manufacturing, food and beverage, and automotive industries. Its combination of touch and key input makes it suitable for environments where operators may be wearing gloves or where precise tactile feedback is preferred. The compact panel cutout dimensions allow integration into standard control cabinet doors and operator stations.
Technical Specifications
| Display Size | 5.7 inch |
|---|---|
| Display Resolution | 320 x 240 pixels |
| Display Type | STN LCD |
| Touch Technology | Resistive touchscreen with membrane keypad |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | Approx. 8 W |
| Communication Interface | MPI/PROFIBUS DP, RS-422/RS-485 |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 10% to 90% (non-condensing) |
| IP/Protection Rating | IP65 (front), IP20 (rear) |
| Mounting | Panel mounting |
| Series/Product Family | SIMATIC OP 177B |
| Certifications | CE, UL, cULus |
| Engineering Software | WinCC flexible 2005 or higher |
Common Error Codes & System Events
- Event ID: 1000
- Communication error between the HMI panel and the connected PLC or controller. The connection has been interrupted or cannot be established.
Check MPI/PROFIBUS DP cable connections and termination resistors. Verify PLC address settings and baud rate configuration in WinCC flexible. Ensure the PLC is in RUN mode. - Event ID: 1003
- Tag read error. The HMI panel is unable to read a configured tag from the controller.
Verify that the tag address configured in WinCC flexible matches the actual PLC data block or memory address. Check that the PLC program contains the referenced variable. - Event ID: 1004
- Tag write error. The HMI panel is unable to write a value to the configured controller tag.
Check that the target PLC address is not write-protected. Verify tag configuration in WinCC flexible and confirm the PLC is in a state that accepts write commands. - Event ID: 10000
- Runtime software error or project loading failure. The panel runtime has encountered an inconsistency in the loaded project.
Reload the project from the engineering PC using WinCC flexible. If the error persists, perform a factory reset and re-transfer the project. - Event ID: 20000
- System memory low. The panel's available runtime memory is insufficient for the current project.
Reduce the number of active screens, alarms, or recipe entries in the project. Optimize the project in WinCC flexible to reduce memory usage. - Event ID: 40000
- Printer communication error. The panel cannot communicate with the configured printer.
Check printer cable connections and verify printer configuration settings in the panel's control panel. Ensure the correct printer driver is selected. - Event ID: 50000
- Backup/restore error. An error occurred during project backup or restore operation via memory card.
Check that the memory card is correctly inserted and not write-protected. Format the memory card if necessary and retry the backup or restore operation.
Frequently Asked Questions
Which PLCs are compatible with the Siemens 6AV6355-1AA47-7CJ4 OP 177B?
The OP 177B is compatible with Siemens SIMATIC S7-200, S7-300, and S7-400 PLCs via MPI or PROFIBUS DP. It also supports communication with S5 controllers and selected third-party systems via RS-422/RS-485.
What engineering software is required to configure this panel?
The OP 177B is configured using Siemens WinCC flexible 2005 or a later version. Projects are transferred to the panel via a PC/PPI cable, MPI adapter, or Ethernet adapter depending on the available interface.
What is the supply voltage for the 6AV6355-1AA47-7CJ4?
This panel operates on a 24 V DC supply voltage. The power consumption is approximately 8 W under typical operating conditions.
Is the OP 177B suitable for outdoor installation?
The OP 177B has an IP65 rating on the front face, providing protection against dust and water jets, but it is not rated for direct outdoor exposure to sunlight or extreme temperatures. It is intended for installation in control cabinet doors or operator stations in indoor industrial environments.
Does the OP 177B support recipe management and alarm logging?
Yes, the OP 177B supports recipe management, alarm logging, and trend display functions as part of its standard runtime capabilities when configured through WinCC flexible.
Troubleshooting
Display remains blank after power on
Measure the 24 V DC supply voltage at the panel's power connector. Check for correct polarity. Inspect the panel for any visible damage to the power input terminals.
Ensure the 24 V DC supply is stable and within tolerance. If the supply is correct but the display remains blank, the internal power supply or backlight inverter may have failed and the unit should be sent for repair or replacement.
Panel displays 'No connection to PLC' or communication error on startup
Check the MPI or PROFIBUS DP cable connections at both the panel and PLC ends. Verify bus termination is correctly applied at both ends of the network. Confirm the PLC address and baud rate settings match the project configuration.
Replace or reseat the communication cable. Correct the bus address and baud rate in WinCC flexible and retransfer the project. Ensure only the two physical ends of the bus have termination resistors enabled.
Touchscreen does not respond or responds inaccurately
Attempt to recalibrate the touchscreen using the panel's built-in calibration utility accessible from the Windows CE control panel or startup menu. Check for physical damage or contamination on the screen surface.
Clean the screen surface with a soft, dry cloth. Run the touchscreen calibration procedure. If calibration does not resolve the issue, the touchscreen overlay may need replacement.
Project transfer from PC fails or times out
Verify the transfer cable type and connection. Confirm the panel is in transfer mode, which can be activated via the panel's startup menu or control panel settings. Check that the correct communication port and transfer settings are selected in WinCC flexible.
Switch the panel to transfer mode manually via the startup menu. Ensure the correct COM port or MPI adapter is selected in WinCC flexible transfer settings. Try a different cable or adapter if the issue persists.
Panel resets or reboots unexpectedly during operation
Monitor the 24 V DC supply for voltage dips or instability under load. Check the operating environment temperature against the panel's rated range of 0 °C to +50 °C. Review the alarm log for any recorded system events prior to the reset.
Stabilize the power supply and ensure adequate current capacity. Improve cabinet ventilation if overtemperature is suspected. If the issue persists without an identifiable cause, reload the project and consider returning the unit for inspection.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AG1642-0BD01-4AX0 TP177B
€ 555,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3607-1NH00-0AX0 OP7
€ 615,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1NK00-2AX0 SIMATIC OP 27
€ 749,00 – € 964,00Price range: € 749,00 through € 964,00Select options This product has multiple variants. The options may be chosen on the product page