Siemens 6AG1124-1MC01-4AX0 SIPLUS HMI TP700 Comfort
€ 1.889,00
The Siemens SIPLUS HMI 6AG1124-1MC01-4AX0 is a ruggedized variant of the SIMATIC HMI TP700 Comfort panel, belonging to the SIPLUS extreme product family designed for use in harsh environmental conditions. It features a 7-inch widescreen TFT touch display and is engineered to operate reliably in environments with extended temperature ranges, increased condensation resistance, and exposure to corrosive atmospheres. This panel is part of the Siemens Comfort Panel generation, offering advanced visualization capabilities for industrial automation systems.
The 6AG1124-1MC01-4AX0 is equipped with a resistive touch screen and supports a display resolution of 800 x 480 pixels with 16 million colors. It provides a comprehensive set of communication interfaces including PROFINET, MPI/PROFIBUS DP, USB, and Ethernet, enabling seamless integration with SIMATIC S7 PLCs and other controllers. The panel features 12 MB of user memory for project data, supports WinCC (TIA Portal) engineering, and includes an SD card slot for data logging and project transfer. Its robust design complies with extended environmental protection standards beyond those of the standard TP700 Comfort.
The SIPLUS HMI TP700 Comfort is commonly deployed in industries such as chemical processing, food and beverage, water treatment, and offshore applications where standard HMI panels cannot withstand the environmental stresses present. It is particularly suited for control cabinets exposed to condensation, aggressive gases, or wide temperature fluctuations. The panel's extended environmental ratings make it the preferred choice for outdoor installations and demanding industrial environments where continuous reliable operation is critical.
Technical Specifications
| Display Size | 7 inch |
|---|---|
| Display Resolution | 800 x 480 pixels (WVGA) |
| Display Colors | 16,777,216 (16 million) |
| Display Type | TFT widescreen |
| Touch Technology | Resistive touch screen |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | Typically 7.5 W |
| Communication Interface | PROFINET (2x RJ45), MPI/PROFIBUS DP (RS 422/485), 2x USB, 1x Ethernet |
| User Memory | 12 MB |
| Operating Temperature | -20 °C to +60 °C (SIPLUS extended range) |
| Storage Temperature | -40 °C to +70 °C |
| Relative Humidity | 5% to 95% (with condensation, SIPLUS rated) |
| IP/Protection Rating | IP65 (front), IP20 (rear) |
| Mounting | Panel mounting |
| Certifications | CE, UL, cULus, ATEX (depending on variant) |
| Series/Product Family | SIPLUS extreme / SIMATIC HMI Comfort Panels |
Common Error Codes & System Events
- Event ID: 10000
- Communication error between HMI panel and PLC. The configured connection to the controller cannot be established or has been lost.
Check PROFINET or MPI/PROFIBUS DP cable connections and termination resistors. Verify PLC is powered and running. Confirm correct communication parameters in WinCC project. - Event ID: 10001
- Connection to PLC interrupted during runtime. Tags cannot be read or written.
Inspect network cables and connectors. Check PLC program status. Restart the HMI project and verify IP address or MPI address configuration. - Event ID: 20000
- Tag read error. A configured tag address cannot be read from the controller.
Verify the tag address in the WinCC project matches the actual PLC data block or memory address. Check PLC program for address changes. - Event ID: 40000
- Project download error. Transfer of the WinCC project to the HMI panel failed.
Check USB or Ethernet transfer cable. Ensure the panel is in transfer mode. Verify sufficient user memory is available on the device. - Event ID: 50000
- Internal system error. An unexpected software fault has occurred in the HMI runtime.
Restart the HMI panel. If the error persists, reload the WinCC project. Perform a factory reset if necessary and re-transfer the project. - Event ID: 70000
- SD card error. The inserted SD card cannot be read or is not recognized.
Remove and reinsert the SD card. Verify the card is formatted correctly (FAT32). Replace the SD card if the error persists. - Event ID: 110000
- Alarm buffer overflow. The number of pending alarms exceeds the buffer capacity of the HMI panel.
Acknowledge and clear active alarms. Review alarm configuration in WinCC to reduce simultaneous alarm triggers. Increase alarm buffer size in project settings if possible.
Frequently Asked Questions
What PLC systems are compatible with the SIPLUS HMI 6AG1124-1MC01-4AX0?
This panel is compatible with Siemens SIMATIC S7-1200, S7-1500, S7-300, and S7-400 PLCs via PROFINET or MPI/PROFIBUS DP. It can also communicate with third-party controllers using standard protocols supported by WinCC.
What software is required to program or configure this HMI panel?
The panel is configured using Siemens WinCC (TIA Portal). It is compatible with TIA Portal V13 and later versions. The project is transferred to the panel via USB, Ethernet, or SD card.
What makes the SIPLUS variant different from the standard SIMATIC TP700 Comfort?
The SIPLUS extreme variant (6AG1124-1MC01-4AX0) is designed for extended environmental conditions including wider operating temperature ranges, resistance to condensation, and tolerance of corrosive atmospheres. It undergoes additional testing and conformal coating compared to the standard TP700 Comfort.
What is the operating voltage of this HMI panel?
The panel operates on 24 V DC supply voltage, which is standard for SIMATIC HMI Comfort Panels.
Does this panel support data logging and recipe management?
Yes, the TP700 Comfort supports data logging and recipe management functions within WinCC. Data can be stored internally or on an external SD card or USB storage device.
Troubleshooting
Display remains blank after power on
Measure 24 V DC supply voltage at the power connector. Check internal fuse if accessible. Observe whether the backlight illuminates briefly at startup.
Ensure the 24 V DC supply is within tolerance (20.4–28.8 V DC). Replace the power supply if voltage is absent. If backlight fails immediately, the display or inverter board may require replacement.
Touch screen does not respond or responds inaccurately
Check for physical damage or contamination on the touch surface. Attempt to recalibrate the touch screen via the panel's Start Center menu.
Clean the touch surface with a soft, dry cloth. Perform touch screen recalibration in the Start Center. If calibration fails repeatedly, the resistive touch layer may be damaged and the display assembly should be replaced.
HMI panel cannot establish communication with the PLC
Verify cable connections on PROFINET or MPI/PROFIBUS DP ports. Check IP address or MPI address settings on both the panel and PLC. Use the panel's diagnostic tools to ping the PLC.
Correct any IP address conflicts or MPI address mismatches. Replace damaged cables or connectors. Ensure the PLC is in RUN mode and the correct communication driver is configured in the WinCC project.
Project transfer fails during download from TIA Portal
Check the transfer connection type (USB or Ethernet). Verify the panel is set to transfer mode via the Start Center. Confirm the TIA Portal version is compatible with the panel firmware version.
Switch the panel to transfer mode manually via Start Center. Update panel firmware if a version mismatch exists. Try an alternative transfer method (e.g., use SD card if USB fails).
Panel repeatedly restarts or crashes during runtime
Check for overheating by measuring ambient temperature around the panel. Review the WinCC project for script errors or excessive tag polling rates. Check the 24 V DC supply for voltage fluctuations.
Ensure adequate ventilation around the panel and verify ambient temperature is within the rated operating range. Stabilize the power supply. Simplify or debug WinCC scripts and reduce tag update cycles if the project is overloading the processor.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AG1545-0BC15-2AX0 SIPLUS HMI TP900
€ 875,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AG1642-0BD01-2AX0 TP177B
€ 714,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1NK00-0AX0 SIMATIC OP 27
€ 755,00Select options This product has multiple variants. The options may be chosen on the product page