Siemens 6AV6545-0DB10-0AX0 TP270
€ 1.894,00 – € 2.549,00Price range: € 1.894,00 through € 2.549,00
The Siemens 6AV6545-0DB10-0AX0 is a Touch Panel 270 (TP270) HMI device belonging to the SIMATIC Panel family. This unit features a 10.4-inch TFT color display and is designed for operator control and monitoring tasks in industrial automation environments. It is part of the SIMATIC HMI product line developed by Siemens and is configured and programmed using WinCC flexible software.
The TP270 with part number 6AV6545-0DB10-0AX0 is equipped with a resistive touchscreen interface and a 10.4-inch TFT display capable of rendering 256 colors at a resolution of 640 x 480 pixels (VGA). The panel includes an MPI/PROFIBUS DP interface for direct connection to Siemens SIMATIC S7 PLCs, as well as a serial RS-232/RS-422/RS-485 interface for third-party controller connectivity. It features 4 MB of user memory for project data and supports recipe management, trend displays, alarm logging, and multi-language operation.
The TP270 is widely deployed in machine-level operator panels across industries such as manufacturing, packaging, food and beverage, and automotive assembly. Its robust industrial housing, wide operating temperature range, and compatibility with the SIMATIC S7 controller family make it well suited for integration into existing Siemens automation architectures. The panel is typically mounted in a control cabinet door or operator console cutout and provides a reliable human-machine interface for process visualization and control.
Technical Specifications
| Display Size | 10.4 inch |
|---|---|
| Display Resolution | 640 x 480 pixels (VGA) |
| Display Type | TFT color LCD |
| Display Colors | 256 colors |
| Touch Technology | Resistive touchscreen |
| Input/Operating Voltage | 24 V DC |
| Power Consumption | Max. 25 W |
| User Memory | 4 MB |
| Communication Interface | MPI/PROFIBUS DP, RS-232/RS-422/RS-485 |
| Operating Temperature | 0 °C to +50 °C |
| Storage Temperature | -20 °C to +60 °C |
| Relative Humidity | 10% to 90% (non-condensing) |
| IP Rating (Front) | IP65 |
| IP Rating (Rear) | IP20 |
| Mounting | Panel mounting |
| Certifications | CE, UL, cULus |
Common Error Codes and System Events
- Event ID: 10000
- Communication error between the HMI panel and the connected PLC. The configured connection cannot be established.
Check MPI/PROFIBUS DP cable connections and termination resistors. Verify the PLC address and baud rate settings match the HMI project configuration. Ensure the PLC is powered and in RUN mode. - Event ID: 10001
- Connection to PLC interrupted during operation. The HMI lost communication with the controller.
Inspect cable integrity and connector seating. Check for electromagnetic interference sources near the communication cable. Restart both the HMI and PLC if the connection does not recover automatically. - Event ID: 20000
- Project download error. The project transfer from the engineering PC to the HMI panel failed.
Verify the transfer cable is correctly connected and the HMI is in Transfer mode. Check that the WinCC flexible version is compatible with the panel firmware version. Ensure sufficient free memory on the panel. - Event ID: 40000
- System memory low. Available memory for runtime operation is insufficient.
Reduce the project size by removing unused screens, graphics, or recipe data. Archive log data and clear the alarm buffer. Consider upgrading to a panel with greater memory capacity if the issue persists. - Event ID: 50000
- Internal device error or hardware fault detected during self-test at startup.
Perform a full power cycle. If the error persists, back up the project and perform a factory reset. Contact Siemens technical support or arrange for unit repair if the fault recurs after reset. - Event ID: 60000
- Tag update error. One or more configured tags could not be read from or written to the PLC.
Check that the PLC data block addresses referenced in the HMI project exist and are accessible. Verify data type compatibility between HMI tags and PLC variables. Review the connection configuration in WinCC flexible. - Event ID: 70000
- Recipe data error. A recipe record could not be read, written, or transferred correctly.
Check the recipe configuration in WinCC flexible for correct data block references. Ensure the PLC data blocks are not write-protected. Verify that the recipe data format matches the PLC variable types.
Frequently Asked Questions
Which programming software is used to configure the TP270 6AV6545-0DB10-0AX0?
The TP270 is configured using Siemens WinCC flexible software. The appropriate version must be used to ensure compatibility with the panel firmware.
Which Siemens PLCs are directly compatible with this HMI panel?
The TP270 connects directly to SIMATIC S7-200, S7-300, and S7-400 PLCs via the MPI or PROFIBUS DP interface. Third-party controllers can be connected via the RS-232/RS-422/RS-485 serial interface using appropriate drivers.
What is the supply voltage for the 6AV6545-0DB10-0AX0?
The panel operates on 24 V DC. The power supply must be capable of providing at least 25 W to ensure stable operation.
What is the front panel protection rating of this HMI?
The front of the TP270 panel is rated IP65, making it resistant to dust ingress and low-pressure water jets. The rear of the unit is rated IP20.
Can the TP270 be used with WinCC Runtime or TIA Portal?
No, the TP270 is not compatible with TIA Portal or WinCC Runtime. It must be programmed exclusively with WinCC flexible, which is the legacy engineering tool for this panel generation.
Troubleshooting
Display remains blank after power is applied
Measure the 24 V DC supply voltage at the power connector on the rear of the panel. Check that the voltage is within the specified tolerance. Inspect the internal fuse if accessible.
Correct any supply voltage issues at the power source. If the supply voltage is correct and the display remains blank, the backlight inverter or internal power supply board may have failed and the unit should be sent for repair.
Touchscreen does not respond or responds inaccurately to touch input
Check whether the touch response is completely absent or merely offset. An offset response typically indicates a calibration issue, while complete non-response may indicate a hardware fault.
Access the panel's Control Panel via the Start Center and run the touchscreen calibration routine. If calibration does not resolve the issue, clean the screen surface and retest. Persistent hardware faults require panel repair or replacement of the touch foil.
HMI cannot establish communication with the S7 PLC
Verify the MPI or PROFIBUS DP cable is correctly wired and terminated. Check the bus address configured in the HMI project matches the physical PLC address. Confirm the baud rate settings are consistent on both devices.
Correct any wiring or termination errors. Adjust the PLC address or baud rate in the WinCC flexible project and re-download to the panel. Replace the communication cable if physical damage is found.
Project transfer from PC to HMI panel fails
Confirm the HMI is in Transfer mode (accessible via the Start Center). Check the PC-to-panel connection cable and the selected transfer channel (MPI, serial, or Ethernet if applicable). Verify the WinCC flexible version compatibility.
Switch the panel to Transfer mode manually before initiating the download. Use a known-good transfer cable. Ensure the WinCC flexible software version supports the TP270 panel type and that the project does not exceed the panel's available memory.
Panel repeatedly restarts or crashes during runtime
Check for supply voltage fluctuations using a multimeter or oscilloscope at the 24 V DC input. Review the alarm and event buffer for recurring system event codes that may indicate the root cause.
Stabilize the power supply and ensure adequate current capacity. If voltage is stable, perform a firmware update or factory reset and re-download the project. If the issue persists, the unit likely has an internal hardware fault requiring professional repair.
| Condition | Repair, Used, Refurbished, New in box (sealed) |
|---|
Related products
-
Siemens 6AV6545-0AA15-2AX0 TP 270
€ 399,00 – € 1.149,00Price range: € 399,00 through € 1.149,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV6642-8BA10-0AA0 TP177B
€ 964,00 – € 1.611,00Price range: € 964,00 through € 1.611,00Select options This product has multiple variants. The options may be chosen on the product page -
Siemens 6AV3627-1NK00-2AX0 SIMATIC OP 27
€ 749,00 – € 964,00Price range: € 749,00 through € 964,00Select options This product has multiple variants. The options may be chosen on the product page